AD-SW 3 GL

Description

The AD-SW 3 GL is used to measure high AC currents, such as secondary currents from large current transformers (e.g. 0...5A AC). The device contains 3 measuring transformers for contactless measurement of all three phase currents. The lines to be measured are fed horizontally through the device. Three small signal outputs are available for evaluation, which represent the measured current. The three output signals are galvanically coupled but separated from the input and the supply with high isolation. The AC sine wave voltage outputs, which follow the input signal 1:1 up to the maximum bandwidth of the device, can be customized. The integrated wide range power supply allows a wide supply voltage range with low self-heating.

AD-SW 3 GL

Application

Measurement of AC currents and conversion into measurable signals for subsequent measurement technology.
Areas of application e.g. in transformer monitoring.

Specific characteristics

  • through-hole transformer for current measurement
  • contactless current measurement
  • Sine outputs (follow the input signals 1:1)
  • wide range power supply

Business data

Order number
AD-SW 3 GL Output: sine wave signal - evaluation according to customer data in plain text
Identifiers
Customs tariff number / country of origin 8543 70 90 / Deutschland

Information

Downloads
Safety instructions pdf ad-safety-instructions.pdf (43 kB)

Technical specifications

Input
Measuring range Max. 0 ... 5 A ACeff / 7,07 A Amplitude - customized
Max. measurable harmonic 100 (5 kHz)
Conductor thickness (outer diameter) <6 mm (Bare wires not allowed to pass through!)
Permanent overload 120 % of the rated value
Temporary overload (1s) Rated value x 20
Output
Output range 0 ... 10 V AC amplitude (7,07 V ACeff)
Min. burden 10 kOhm
Phase backfill Input/Output Output < 1° lagging
Residual ripple Ca. 20 mV
Cut-off frequency
-3 dB limit Ca. 10 kHz
Accuracy
Unit <0,5 %
Temperature influence <100 ppm / K
Zero point error <0,3 %
Supply
Supply voltage AC 50 ... 253 V AC
Nominal voltage AC 230 V AC
Supply voltage DC 20 ... 253 V DC
Nominal voltage DC 24 V DC
Power consumption AC / DC 3,6 VA / 1,8 W
Housing
Connection method input Feed-through converter
Connection method Screw clamp
Manner of fastening 35 mm DIN rail 35mm
Dimensions (WxHxD) 18x75x103 mm
Weight Ca. 150 g
Environmental conditions
Ambient temperature -10 ... 50 °C
Storage and transport -10 ... 70 °C (no condensation)
EMC
Product family standard EN 61326-1
Emitted interference EN 55011, CISPR11 Cl. B, Gr. 1
During checking, slight signal deviations are possible
Electrical safety requirements
Product family standard EN 61010-1
Overvoltage category II
Pollution degree 2
Safety measurement EN 61010-2-030
Measurement category CAT III
Galvanic isolation, test voltages
Input / output 3,51 kV AC + Test voltage of the cable insulation (1 min)
Input / supply unit 4 kV AC (1 min)
Output / supply unit 3 kV AC (1 min)
Galvanic isolation, working voltage
Input / output 300 V DC or ACeff
Input / supply unit 300 V DC or ACeff
Output / supply unit 300 V DC or ACeff
Protective systems
Input/output Over voltage and over current
Power supply Over voltage, over current and over temperature

Block and wiring diagram

AD-SW 3 GL

Dimensions

AD-SW 3 GL

Circuit examples

AD-SW 3 GL

CAD / CAE Daten

CAD model is not yet available for this product.

The CAD product overview can be found at: adamczewski.partcommunity.com

Cookie settings
made with ♡ by andres.media